| Type of Protection | Ex eqm (Increased safety Powder filling Encapsulation) |
| Area Classification | Zone 1 and Zone 21 |
| ATEX Classification | Group II Category 2 G D |
| IEC Ex | IECEx ITS 03.0005 |
| ATEX | EC Type Examination Certificate Baseefa04ATEX0220 |
| Enclosure | GRP body with polycarbonate cover and brass suspension points |
| Reflector/Geartray | White polyester painted zinc coated steel |
| Entry | 4 x M20 cable entries, two at each end |
| Termination | 3 core 6mm sq max. conductor with looping and 16A rating through wiring (4 core for emergency) |
| Installation | Two M8 tapped brass inserts located on rear of body |
| Lampholder | G13 (Bi-pin) |
| Lamp Type | T8 tubular fluorescent |
| Control Gear | High Frequency (EOL) |
| Relamping | Quick release diffuser clamps and hinged cover |
| Burning Position | Universal |
| Ingress Protection | IP66/IP67 to EN 60529 and deluge tested to DTS-01 |
| Electrical Supply | 220V - 254V 50/60Hz, |
| Battery | Internal Ni-Cd Battery (6V 4 Ah) |
| Duration | 90 minutes to EN60598-2-22 (as standard) 3 hour option available |
| Emergency Output | 30% of one lamp (18W), 50% HEO Option 25% of one lamp (36W), 45% HEO Option |