| Type of Protection | Ex e mb q (Increased safety Encapsulation Powder filling) |
| Area Classification | Zone 1 and Zone 21 |
| ATEX Classification | Group II Category 2 GD |
| ATEX | EC Type Examination Certificate Baseefa04ATEX0220 |
| Coding | II 2 GD Ex e mb q IIC T4 Tamb 55ºC (45ºC for emergency version) |
| Enclosure | Stainless steel body with polycarbonate cover |
| Reflector/Geartray | White polyester painted zinc coated steel |
| Entry | 4 x M20 cable entries, two at each end |
| Termination | Quick release terminals - 3 core 4mm² max. conductor with looping and 16A rating through wiring (4 core for emergency). 6mm² terminations available, contact sales |
| Installation | Two M8 tapped stainless steel inserts located on rear of body |
| Lampholder | G13 (Bi-pin) |
| Lamp Type | T8 tubular fluorescent |
| Control Gear | High Frequency |
| Relamping | Quick release diffuser clamps and hinged cover |
| Burning Position | Universal |
| Ingress Protection | IP66 to EN 60529 |
| Electrical Supply | 220V-254V 50/60Hz, 220V - 300V dc non-emergency only |
| Battery | Internal Ni-Cd Battery (6V 4 Ah) |
| Duration | 90 minutes to EN60598-2-22 |
| Emergency Output | 50% of one lamp (18W)
25% of one lamp (36W), 45% HEO Option |