| Type of Protection | Ex d (flameproof), Ex dm (flameproof, encapusulation) emergency version |
| Area Classification | Zone 1 and 21 areas |
| ATEX Classification | Group II Category 2 G D |
| ATEX | SIRA05ATEX1299X |
| Coding | Ex II 2 G D EEx d IIC (for 8W & 18W versions) Ex II 2 G D EEx d IIB (for 36W & 58W versions) |
| Enclosure | LM6 aluminium die cast alloy |
| Reflector/Geartray | Borosilicate glass overtube, painted steel reflector |
| Entry | 2 x M20 cable entries |
| Termination | 3 core 4mm sq max. conductor with looping 4 core on emergency version (no looping on emergency) |
| Installation | Via steel support rail |
| Lampholder | G13 Bi-pin |
| Lamp Type | T8 Bi-pin fluorescent |
| Control Gear | High Frequency (EOL) |
| Relamping | Two socket head screws and tapered spigotted flamepath |
| Burning Position | Universal |
| Ingress Protection | IP66, IP67 and IP68 |
| Electrical Supply | 220V - 254V, 47/63Hz AC/DC
100V - 130V, 47/63Hz AC/DC |
| Duration | 3 hours to EN 60598-2-22 (standard |
| Emergency Output | 2 x 18W = 14%
2 x 36W = 7%
2 x 58W = 5%
|