| Type of Protection | Ex eqm (Increased safety Powder filling Encapsulation) T4 -20ºC to +50ºC Ta 95ºC DJP A21 -20ºC to +55ºC |
| Area Classification | Zone 1 and Zone 21 |
| ATEX Classification | Group II Category 2 G D |
| IEC Ex | IECEx ITS 03.0006 |
| ATEX | EC Type Examination Certificate Baseefa04ATEX0286 |
| Enclosure | White polyester painted zinc coated steel body and frame. Silicone rubber gasket. Clear polycarbonate diffuser |
| Reflector/Geartray | White polyester painted zinc coated steel |
| Entry | 3 x 21mm holes, two at one end and one at the other end |
| Termination | 3 core 6mm2 max conductor with looping and through wiring facility (4 core on emergency) |
| Installation | Fixed side brackets with swing out arms, with provision for rod mounting |
| Lampholder | G13 (Bi pin) |
| Lamp Type | T8 tubular fluorescent |
| Control Gear | High Frequency (EOL) |
| Relamping | Via front cover, secured by pan head slotted screws |
| Burning Position | Horizontal |
| Ingress Protection | IP65 to EN 60529 |
| Electrical Supply | 220V - 254V 50/60Hz 220V - 300V dc non-emergency only |
| Battery | Internal Ni-Cd battery (6V 4 Ah - 18W, 6V 7Ah - 36W) |
| Duration | 90 minutes to EN60598-2-22 |
| Emergency Output | 50% of one lamp (18W) 25% of one lamp (36W), 45% HEO Option |