| Type of Protection | Ex de (Flameproof, Increased Safety) |
| Area Classification | Zone 1 and Zone 2 areas |
| ATEX Classification | Group II Category 2 G |
| IEC Ex | Pending |
| ATEX | EC Type Examination Certificate
BAS01ATEX2309 |
| Coding | Ex II 2 G EEx de IIB |
| Enclosure | Aluminium alloy LM6. All fastenings stainless
steel. Toughened glass bowl |
| Reflector/Geartray | High purity anodised aluminium |
| Entry | 2 x M20 cable entries |
| Termination | 3 core 6mm sq max. conductor with looping |
| Installation | Stirrup mounting bracket |
| Lampholder | E40 |
| Lamp Type | HPS, Metal Halide, Mercury Vapour and GLS |
| Control Gear | Internal copper/iron with PFC correction
capacitor |
| Relamping | Access via front glass cover assembly |
| Burning Position | Universal |
| Ingress Protection | IP66/67 |
| Electrical Supply | 220, 230, 240, 254V 50Hz (HID)
110V - 240V ac/dc (GLS) |