| Type of Protection | Ex de (Flameproof Increased Safety) |
| Area Classification | Zone 1 and Zone 21 areas |
| ATEX Classification | Group II Category 2 G |
| ATEX | EC Type Examination Certificate Baseefa02ATEX0168 |
| Coding | II 2 G EEx de IIB (refer to datasheet for T rating and ambient) |
| Enclosure | Aluminium alloy LM6 All fastenings stainless steel. Toughened glass bowl. |
| Reflector/Geartray | High purity anodised aluminium |
| Entry | 2 x M20 cable entries |
| Termination | 3 core 6mm sq max. conductor with looping |
| Installation | Flush or handrail mounting bracket |
| Lampholder | E27 for GLS and HID lamps. G24q for compact fluorescent |
| Lamp Type | HPS, Metal Halide, Mercury Vapour, GLS, Compact Fluorescent, MBTF or QL Induction lamp |
| Control Gear | Internal copper/iron with PFC correction capacitor |
| Relamping | Access via hinged front glass cover assembly |
| Burning Position | Universal |
| Ingress Protection | IP66/67 |
| Electrical Supply | 220, 230, 240, 254V 50Hz - 70 HPS/Metal Halide
220, 230, 240V 50Hz - 80 and 125W MBF/U
250V Max GLS/MBTF
240V - CF
220-240V QL
|