| Type of Protection | Ex nR (Restricted Breathing) |
| Area Classification | Zone 2 and Zone 22 areas |
| ATEX Classification | Group II Catagory 3 G D |
| ATEX | Type Examination certificate BAS01ATEX3239 |
| Coding | II 3 G D EEx nR II
(refer to datasheet for T rating and ambient) |
| Enclosure | White polyester painted zinc coated steel
body and front cover with silicone gasket
and polycarbonate diffuser |
| Reflector/Geartray | High purity anodised aluminium |
| Entry | 2 x 20mm diameter holes |
| Termination | 3 core 6mm sq max. conductor with looping |
| Installation | 4 x 10mm clearance holes |
| Lampholder | E40 |
| Lamp Type | HPS or Metal Halide |
| Control Gear | Internal copper/iron ballast with ignitor and PFC correction capacitors |
| Relamping | Access via front cover secured by eight stainless steel screws |
| Ingress Protection | IP65 |
| Electrical Supply | 220, 230, 240, 254V 50Hz |